848, Construct new stable, corrall,, Studies & ReportsmiWILLDANextending yeotechnical e° r May 14, 2014 Project No: 101749-6003 GEOTECHNICAL ENGINEERING REVIEW Submitted to: Elroy Kiepke, Willdan Engineering Project Location: Report Reviewed: Review Status: Review Comments #9 Chuckwagon Road City of Rolling Hills, California "Limited Soil Engineering Investigation and Report for Proposed Detached One -Story Stable with Basement and New 2:1 Fill Slope at # 3 Chuckwagon Road, Rolling Hills, California" Dated December 6, 2013, Prepared by T.I.N. Engineering Company, File No.: 101779 NOT APPROVED from Geotechnical View point. Approval of the subject report is subject to receipt of satisfactory response to the following review comments 1. Provide general site geology and fault location map with the property location. 2. Section B-B' should be extended to the toe of the existing natural slope, or use the depicted Section A/3 to show subsurface condition. Please correct the list of enclosures, Cross Section A -A' or B-B'? 3. Thickness of Colluvium and depth to bedrock should be explored and reasonably established for slope stability and depth of remedial excavation including the proposed fill key. 4. The details shown on Plate 9 should be depicted on the above cross sections; depth and width of key including the benching into competent bedrock. 5. Provide appropriate slope stability analyses, for static/seismic and global/surficial conditions. 6. Provide lateral pressure parameters due to seismic forces on free standing and basement walls. 7. Provide a detail for the retaining wall backfill including recommended drain pipe material; SDR designation. 8. The sheets C2.0 of Grading Plans, shows fill slope key embedded into firm Colluvium. The subject details including cross sections should be corrected upon input from Geotechnical Engineer. 9. The final approval of grading plans are subject to review and approval of a response report to above comments 10. The geotechnical consultant of record must review the grading and foundation plans and sign and stamp the plans in verification of the recommendations. 11. The approved report must be referenced on the grading and foundation plans. Engineering I Geotechnical 1 Environmental I Sustainability Financial I Homeland Security Phone 714.634.3318 I fax: 714.634.3372 11515 South Sunkist Street, Suite E, Anaheim, CA 92806 I www.willdan.com Respectfully submitted, WILLDAN GEOTECHNICAL Ross Khiabani, PE, GE Director of Geotechnical Engineering Services C 37156, GE 2202 Distribution: Addressee (via e-mail) ADDRESS: PROJECT: RETAINING WALLS: CITY OF ROLLING HILLS No. 2 Portuguese Bend Road Rolling Hills, CA 90274 Willdan: (562) 908-6200 CITY OF ROLLING HILLS SINGLE-FAMILY RESIDENTIAL CORRECTIONS LIST 2014 Los Angeles County Residential Building Code with Local Amendments #9 CHUCKWAGON FOUNDATION ONLY -RETAINING WALLS FOR FUTURE STABLES WITH UNIT ABOVE ON HILLSIDE SLOPE HEIGHT TO - 9 LENGTH 102 FEET FEET OWNER: STEVE COOLEY ARCHITECT: ROSS BOLTON, PE- BRAD MOSER, PE CONTACT: PHONE: (310) 325-5580 WILLDAN PLAN CHECKER: ART PEREZ, PE WILLDAN TELEPHONE #: (562) 908-6244 FAX #: 562-695-2120 HOURS: M_TH 7:30 AM- 4:30PM EMAIL: aperez@willdan.com PLAN CHECK No.: 00229 VALUATION: TYPE: $50,000.00 VB OCCUPANCY: U ENGINEER: SOILS/GEO: TELEPHONE: BOLTON ENGINEERING- BRADLEY MOSER TIN ENGINEERING CO. (310) 325-5580 1ST CHK DATE: 10-30-14 2ND CHK DATE: 1-08-15 3RD CHK DATE: 4TH CHK DATE: APPROVED: Your application for a permit, together with the submitted plans, has been examined and the issuance of a permit is withheld for the reasons set forth below. The approval of plans does not permit the violation of any section of the Building Codes or other local ordinance or state law. FYI: Reference numbers in brackets [Rxxx] refer to Code Section of the 2014 edition of the Los Angeles County Residential Code, Building Code (for structural only) [BC], Plumbing Code [PC], Mechanical Code [MC], and Electric Code [EC]; Green Building Code [GC], 2010 California Energy Code [EnC]; Asterisk [*] refers to local amendments. (2013 CEnC not effective until July 1, 2014). INSTRUCTIONS: • Numbered comments below are correction items or comments applicable to this plan review. Please revise plans as indicted by each correction or comment. • In the left-hand margin of each correction or comment, please indicate the sheet number and detail or note number on the plans where the corrections/revisions were made. Please be as specific as possible. Macintosh HD:Users:yolantaschwartz:Library:Caches:Temporaryltems:Outlook Temp:Rolling Hills-PC#00229-VER#1-FOUNDATION ONLY, RETAINING WALLS FOR stable with unit above on sloped ground-2014 LaCo.docx 7-16-08 Page 1 of 7 • All comments on plans are considered part of the plan check and must be returned at the time of resubmittal. Resubmit to the City this "corrections list", the original "check set" of .plans with three sets of revised plans and all originally submitted and newly revised documents for recheck. • The plan checker is available for conference and phone calls at the numbers and hours indicated above. Please contact the plan checker if you have anv auestions orfor plan review appointments. • Note that Rolling hills Planning Dept and Community Association review stamps are required at each submittal MISSING • The Resolution and the planning review did not address having a dwelling unit over the basement stables. The unit has a % bath with a shower stall. water closet and sink and a kitchen with sink. The office space appears to be a sleeping quarters. The space is to be heated or cooled or both. Energy calcs/details missing, but plans shows insulation MISSING • Recheck Comments: • Correction numbers or letters that are missing have been cleared. • Portions of corrections that have been strikeout have been cleared • Underline portions of corrections need to be address. Corrections remaining are still outstanding. • Bold lettering and highlighted are further clarification /reasons what is needed to show compliance to the correction • Bullets have been added to address the revised calcs and details • Address comments on check set of plans • ALL CORRECTIONS REMAINING ON LIST ARE OUTSTANDING AND NEED TIO BE ADDRESSED GENERAL INFORMATION APPLICATION AND PERMIT PROCESSING 1. At the completion of the Building Plan Review process and prior to obtaining a building or grading permit, submit the following for review and approval to the Rolling Hills Planning Department and Community Association. Return the stamped plans to Willdan Building & Safety for final building approval stamping and permit issuance. a. Three sets of complete final building plans (all sheets). b. Two additional site plans. c. Two grading plans (if applicable). d. In addition, for new SFD's provide a "Statement of Compliance" for any required Landscape Plan. 2. Prior to permit issuance for all habitable residential construction, provide documentation that the applicable School Fees have been paid. A "Certification of Compliance/Payment of Developer Fees" form must be prepared by the developer/owner, the fees must be paid and the school district. must verify the form before the respective permit can be issued. [Palos Verdes Peninsula Unified School District] Macintosh HD:Users:yolantaschwartz:Library:Caches:Temporaryltems:Outlook Temp:Rolling Hills-PC#00229-VER#1-FOUNDATION ONLY, RETAINING WALLS FOR stable with unit above on sloped ground-2014 LaCo.docx 7-16-08 Page 2 of 7 3. Prior to Building Permit issuance, include on the approved sets of plans the City "Certification to Obtain Building Permit" (Administrative of Resolution approval) signed by the agent/owner or the Contractor and City. 4. Application will expire on 10-30-15 (one year after date of application). Building Permit needs to be obtained prior to expiration date, otherwise the application shall expire. [106.4.1.1] 5. Prior to issuance of a grading permit, any incidental or related project buildings/structures shall be submitted for plan review. [RH] 6. Projects requiring a grading permit require a "Pad Certification" prior to the issuance of a building permit. 7. A licensed contractor shall present a Certificate of Workers' Compensation insurance upon Building Permit issuance. REFERRALS AND PROJECT COORDINATION 8. All AGENCY APPROVALS and FEES are required prior to permit issuance. Please see the attached "Agency Referral Sheet" for specific details and additional required agency approvals. a. All new single family dwellings and additions require LACo Fire Dept approval (VHFHSZ, Fire Sprinklers and Brush Clearance). Make separate submittal to LACo Fire and provide approved LACo plans for each of the following: Site Plan (site. driveway, fire flow), Fuel Modification/Brush Clearance and Fire Sprinklers (New construction. This may be a "Deferred Submittal"). b. Water (VHFHSZ) - California Water Service. c. Septic tank/systems (new or revised). — LACo Health. See "Procedures for Application" and complete "Service Request". (See "Septic Systems" in "Plan & Project Coordination" below. d. School Fees: Complete the "Certificate of Compliance/Payment of Developer Fees" for the Palos Verdes Peninsula Unified School District and pay all fees prior to permits. See attached "Agency Referral Sheet" and the Palos Verdes Peninsula Unified School District "Notice to Developers". 9. All Soil, Foundation or Geology report(s) must be approved by city Soils and Geology consultants (Willdan Geotechnical) prior to permits. Provide a copy of final approved geotechnical review report letter by Willdan Geotechnical and all referenced soil reports. Not provided 10. Storm Water Pollution Control: a. Attach the signed/completed "Best Management Practices for Constructing Activities" to the final set of plans prior to permits, or b. Submit the approved Grading Plan including the Storm Water Pollution Control plans. 11. A Grading Permit is required. Provide copy of the approved grading plans prior to final submittal[Appendix J103, RHBC J107] . Not provided 12. Rough grading approval/pad certification is required before a building permit can be issued. [Appendix J105.7] Macintosh HD:Users:yolantaschwartz:Library:Caches:Temporaryltems:Outlook Temp:Rolling Hills-PC#00229-VER#1-FOUNDATION ONLY, RETAINING WALLS FOR stable with unit above on sloped ground-2014 LaCo.docx 7-16-08 Page 3 of 7 ARCHITECT- OR ENGINEER -OF -RECORD 15. Final Plans: Plans are required to be prepared under the supervision of a licensed architect or registered engineer. Final plans prepared by a licensed architect or registered engineer, each sheet of plans must bear the, seal and original signature of the responsible Architect or Engineer. [California Business & Professions Code 5536.1] NATURE OF WORK SCOPE OF WORK 16. A foundation only is a permit that has assumptions of risk. Provide assumption of risk types of letters from the property owner and the engineer of record of the final structure. It is incomplete. Not signed by owner 17. Provide copy of letter and language per the attached guidelines on the plans. Not on plans 19. Identify on the cover sheet the following applicable "Project Building Code Data": [R106.3.3] b. Sprinklers Type of construction as VA ??? PLAN & PROJECT COORDINATION 20. Provide topographic plans that show existing and proposed elevations and slopes on foundation only plans 23. Correct upper portions of retaining walls at back(rear wall) to omit the construction of the wall above the bottom of the future floor/deck/roof so that required hillside anchors can be constructed. Reinforcement can extend above this level as needed. Provide x-referencing to details 24. Correct upper portions of side retaining walls so that future required anchors can be constructed or where they do not extend to the floor/roof framing to have level base/mudsills for wood framing above GRADING / DRAINAGE 26. Provide copy of the approved grading and drainage plans prior to final submittal GREEN BUILDING STANDARDS [GC] 28. Copy the attached "Green Building Code Residential Plan Requirements" on the plan. The items listed below need to be detailed or noted on the plans. The "Construction Notes" are required notes for the contractor. The inspector will verify the applicable features in the field. a. See the attached "Green Building Code Residential Plan Requirements". i. Provide a Storm Water Management Plan or verify that the plan has been submitted to the City Engineer. [4.106.2] ii. Provide a Site Drainage Plan showing existing and proposed elevations and details to: [4.106.3] (a) Direct water to an approved location. (b) Direct water away from the building. (c) Minimum slopes: Concrete or AC —1 %; Landscaped or exposed soil — 2% Macintosh HD:Users:yolantaschwartz:Library:Caches:Temporaryltems:Outlook Temp:Rolling Hills-PC#00229-VER#1-FOUNDATION ONLY, RETAINING WALLS FOR stable with unit above on sloped ground-2014 LaCo.docx 7-16-08 Page 4 of 7 STRUCTURAL REQUIREMENTS [20010 CBC AND CH 35 REFERENCES GENERAL DESIGN INFORMATION [1603] 1. Stamp and signature of licensed design engineer, engineer of record are required on the structural plans and details and the calculations 3. Provide details to address future hold down bolts into the concrete. Provide calcs and details showing assumed vertical tension force at ASD loads 4. Correct all post installed bolts for concrete to have a ICC# that is approved for concrete. Note that they may not have the allowable to resist the demand forces for cracked concrete 5. Correct cast in place SSTB bolts per ESR-2611. Concrete 6. Correct development lengths, Ld for:[ACI 318-11 12.2] The lap show are incorrect Top non contact splice needs to be 82 bar diameters» 47 shown a. For an additional 1.3 factor for top reinforcement. b. For 3,000 psi or less, correct to use 2,500psi, which is approx. a 1.1 increase c. Specify the clear spacing of bars and the clear cover and make the correction for contact splices where required, 1.5 factor. 7. Correct lap splice to address Class B splices with an additional 1.3 factor; For an additional 1.5 factor for contact splice and the factors for Ld above.[ACI 318-11 12.15] 8 Specify the following design information and parameters on the plans and calculations: See correction for latest data a. Correct the design data, The Site Class is C per the soil report, Cs is incorrect and others do not agree with calcs SOILS AND GEOLOGY — REPORTS AND REQUIREMENTS 15. Soil, Foundation or Geology report(s) must be approved by city Soils and Geology consultants (Willdan Geotechnical) prior to permits. Submit a separate application, reports and fees for review. Provide a copy of final approved geotechnical review report letter by Willdan Geotechnical FOR THE ADDENDUM REPORT. 16. Engineering Geologist and/or Geotechnical Engineer to review the foundation planand indicate by a review stamp, their acceptance of the final design. 17. Plans shall include all soils engineer's recommendations and notes. The design values such as soil bearing, frictional coefficient, lateral soil bearing value, should be specified on the plans. Correct passive to 600 psf FOUNDATIONS — GENERAL [CHAPTERS 16 & 18] 19. Building or Footings on or adjacent to ascending or descending slopes steeper than 1V in 3H: [1805.3] a. Building Clearance from Ascending Slopes shall be a minimum of H/2, 15 ft. maximum. [1805.3.1] b. The project soils or geology report shall justify the slope setback. [1805.3.5] Macintosh HD:Users:yolantaschwartz:Library:Caches:Temporaryltems:Outlook Temp:Rolling Hills-PC#00229-VER#1-FOUNDATION ONLY, RETAINING WALLS FOR stable with unit above on sloped ground-2014 LaCo.docx 7-16-08 Page 5 of 7 RETAINING WALL DESIGN 22. Correct the calcs for 9 ft cantilevered wall. The walls is over stressed and the moment is incorrect. The seismic was not included as required The height of the resultant for the seismic needs to be 0.6 to 0.67 xH a. Correct the moment arm for the seismic load to be measure to the resultant that is 2/3 of the height of the stem c. Correct all calcs to for concrete if changed to concrete with increase load factors such as 1.6 for soils & 1.4 for seismic > The live and dead loads on the walls are much higher than the walls will be supporting. Most loads are being carried by wood beams > Provide tabulation of seismic and static loads on each retaining wall. Identify Mu and Vu, that are 1.6 x ASD loads. Explain calcs on pg 24 The ASD loads for 7.25 ft high retain soils are 45x 7.25 x7.25/2 = 1,182.66 lbs and the seismic is 1,162 lbs. That equals 2,344.66 lbs. The calcs show that the total force at the section is 2,1612.3 < 2,344.66 x1.6 = 3,751.45 lbs. Also the Mu is incorrect > Clarify why the stem portion of the program adds 0.5 ft to the height sometimes but does not design for those loads. The above calcs would increase the force to 3,932 lbs > Provide tabulation to show how seismic force was determined and to show that the moment for ASD and LRFD were correctly inputed for a height of 0.67 H 23.9 foot restrained retaining wall a. The loads are incorrect. They should be 42x 1.43x 8.75 ft times 1.6/1.4 since the load combination and the loads are shown as dead loads The load should be approximate 600 plf b. Correct the load from zero to the higher load to be to the 600 plf. As submitted, how can the varying load not equal the uniform load? 25. Correct reinforcement ratio to comply with seismic requirements for high seismic categories. Rho = 0.0025 ea. way Correct side walls 3/S4.4 Will need two curtains of reinforcement to comply 26. Provide details for future anchorage per Hillside requirements on corrections for building. Address rear wall. Not addressed The anchors need to extend perpendicular from the upper portion of the wall to the floor/roof framing. Not vertical 27. Provide design and details for site and/or building retaining walls. a. Redesign lateral pressures on site retaining walls due to earthquake motions. [Sec. 1802.2.7(1803.5.12) & ASCE-11.8.3] Missing from cantilevered rear wall and incorrect from side walls> 6 feet in height c. Provide a foundation drain system that drains to daylight. [1807.4.2] d. Provide cross sections for side partial retaining walls to show upper limits of the concrete wall portion. If it extends to the floor framing, out of plane anchorage is required. Provide elevation views of side walls Macintosh HD:Users:yolantaschwartz:Library:Caches:Temporaryltems:Outlook Temp:Rolling Hills-PC#00229-VER#1-FOUNDATION ONLY, RETAINING WALLS FOR stable with unit above on sloped ground-2014 LaCo.docx 7-16-08 Page 6 of 7 SPECIFICATIONS AND DETAILING 29., Concrete wall anchorage a. Provide details that addresses the future installation of cast in place anchors. Not addressed as required. Need elevation of side walls to determine if required or not 30. Additional corrections may follow based on responses to the corrections and changes made on the corrected plans and calculations on future re -submittals. Macintosh HD:Users:yolantaschwartz:Library:Caches:Temporaryltems:Outlook Temp:Rolling Hills-PC#00229-VER#1-FOUNDATION ONLY, RETAINING WALLS FOR stable with unit above on sloped ground-2014 LaCo.docx 7-16-08 Page 7 of 7